Fan Coil Unit Controller SeriesApplication Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514 ) 321-4150
028-0444-01 www.viconics.com | sales@viconics.com February 2015
APPENDIX A - PASSIVE INFRA-RED SENSOR SPECIFICATIONS
+
-
ref
+
-
ref
+
-
ref
BACnet
thermostat
1
BACnet
thermostat
2
BACnet
thermostat
3
Notes:
• Wiring should be daisy chained
• Always respect polarity
• If using 2 conductors and shielded wires, connect
shield of each feed together on back of Controller
• Only ground shield at one location. Do not connect
shield to reference terminal
No communication wires required
APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION
Setpoints
Tim
e
Unoccupied cool
Occupied cool
Stand-by cool
72°F
76°F
80°F
Movement detected
-
Stand-by timer reset
Into Stand-by mode
-
Unoccupied timer reset
Stand-by
time
Unoccupied
time
Into Unoccupied
mode
Next movement
detected
70°F
62°F
U
noccupied heat
Occupied heat
Stand-by heat
72°F
66°F
70°F
Deadband
Deadband
Deadband
22°C
24.5°C
26.5°C
22°C
21°C 21°C
19°C
16.5°C
BACnet
®
Communication Wiring Wireless Communication
APPENDIX B - OPTIONAL NETWORK SET-UP
Vedere la pagina 60