Parameter Variable Name Function
This network variable output is used to report the Space Comfort
humidity function’s status
Name Valid value
local humidity level 0 to 100% RH
supply humidity level 0 to 100% RH
effective reset humid setpoint 0 to 100% RH
pi humid demand output 0 to 100% demand
Thermostat’s
I/O status
network output
UNVT_rh_status
nvoRHStatus
dehumid output active 0 = Dehumidification not active
1 = Dehumidification active
Setpoint network output
SNVT_temp_p
nvoEffectSetpt
This output network variable is used to monitor the effective
temperature setpoint which may depend on nciSetpoints,
nvoEffectOccup, nviSetpoint and any local setpoint adjustment.
For example, if the occupancy state is unoccupied and the
heat/cool state is heat, the effective setpoint would be equal to
the unoccupied heating setpoint defined in nciSetpoints.
Valid Range: -40 to 100°F (-40 to 37.5°C)
Local setpoint
output
network output
SNVT_temp_p
nvoSetPoint
This output network variable is used to monitor the space
temperature setpoint
Valid Range : 40°F to 100°F (4.5°C to 37.5°C)
The present value is derived by the following
OccHeat Setpoint + ((OccCool Setpoint – OccHeat Setpoint ) / 2)