Configuration parameters
default value
Significance and adjustments
Deh. max. cool.
Default value = 100 %
Maximum cooling valve position when dehumidification is enabled. This
can be used to balance smaller reheat loads installed in regards to the
capacity of the cooling coil.
Range is: 20 to 100 %.
(Models with humidity sensor only).
Deh. lockout
Default value: Enabled
Dehumidification lockout, typically toggled through the network.
This variable enables or disables dehumidification based on central
network requirements from the BAS front end.
Enabled = Dehumidification Authorized
Disabled = Dehumidification Not Authorized
(Models with humidity sensor only).