Configuration parameters
default value
Significance and adjustments
ZigBee
®
channel
Channel selection
Default value = 10
Range is: 10 to 25
This parameter (Channel) is used to link specific Terminal Equipment
Controllers to specific ZigBee
®
coordinators. For every Terminal Equipment
Controller reporting to a coordinator, be sure you set the SAME channel
value both on the coordinator and the Terminal Equipment Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 25.
ZigBee
®
status
( read only )
( Not Det ): ZigBee
®
module not detected
( Pwr On ): ZigBee
®
module detected but not configured
( No NWK ): ZigBee
®
configured but no network joined
( Joined ): ZigBee
®
network joined
( Online ): Communicating