Viconics VT8300 Low Voltage User Interface Guide Manuale Utente Pagina 19

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 45
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 18
19
VT8300 Series
User Interface Guide
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0427-01 www.viconics.com | sales@viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
PARAMETER DETAILS SCREEN 2/7
Configuration Parameters Default Value Significance and Adjustments
Standby mode
Default value: Abs
Standby Mode
Choose which standby setpoints are used for control.
Abs: absolute Standby entered values are used for standby mode.
Offset: offset Occupied setpoints +/- Standby diff. used for standby
mode.
Standby diff.
Default value: 2 °C ( 3 °F )
Standby Difference
When Standby mode is Relative, standby setpoints are calculated as:
Standby cool = Cool setpoint + Standby diff.
Standby heat”= Heat setpoint - Standby diff.
Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )
Vedere la pagina 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 44 45

Commenti su questo manuale

Nessun commento