SETPOINT SETTINGS 2/2
Parameter only displayed on
models with built in humidity
sensor.
SETPOINT PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Default heat
Default value: 22.0 °C (73 °F)
Default Heat
Used for hospitality applications in stand-alone mode only. When devices
are in deep unoccupied mode, any movement detected
by PIR resets actual occupied set points to fresh room default setting.
Default setpoint is used to write to Heating setpoint when thermostat
goes to Unoccupied mode.
Cooling setpoint is set according to Min. deadband; 18.0 to 26.5 °C (65
to 80 °F).
Parameter is only used when Stand-by mode = Rel.
Min. deadband
Default value: 1.5 °C (3 °F)
Minimum Deadband
Minimum deadband value between heating and cooling setpoints
applied only when any setpoints are modified.
Range: 1.0 to 2.5 °C, 0.5 °C increments (2, 3, 4 or 5 °F, 1.0 °F
increments).
Max heating
Default value: 32 °C (90 °F)
Maximum Heating
Maximum occupied and unoccupied heating setpoint adjustment.
Range: 4.5 to 32.0 °C (40 to 90 °F).
Min. cooling
Default value: 12.0 °C (54 °F)
Minimum Cooling
Minimum occupied and unoccupied cooling setpoint adjustment.
Range: 12.0 to 37.5 °C (54 to 100 °F).
Dehumidify
Default value: 50% RH
Dehumidify
Used only if dehumidification sequence is enabled:
Range is: 30-95% RH (models with humidity sensor only).