2/9 Configuration
Fan delay
On
Off
Standy mode
Abs
Standby diff.
2.0 °C
Fan cont. heat
Power-up delay
10 Sec.
CONFIGURATION PARAMETERS SCREEN 2/9
PARAMETER DETAILS SCREEN 2/9
Configuration Parameters Default Value Significance and Adjustments
Fan cont. heat
Fan control
Default value: On
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller in all cases
will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating stages
(terminals W1 & W2) are solicited, will not be energized. The fan in
this case will be controlled by the equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the fan
always on.
ON OR OFF
For multi stage models, fan control applies to W1 & W2
Fan delay
Default value: Off
Fan delay extends fan operation by 60 seconds after the call for
heating or cooling ends.
Valid only for Auto fan mode. On fan mode will leave the fan
always on.
Off or On